SPLIT SYSTEM AIR CONDITIONERINSTALLATION INSTRUCTIONSDO NOT DESTROY. PLEASE READ CAREFULLY & KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.IMPORTANTAT
10Figure 2. Charging Chart for S4BD-060CB Series (5 Ton Units) - TXV Matches20022024026028030032034036038040042044046048050052054056058060075 80 85 90
11ELECTRICAL DIAGRAMS & TABLESRT3T1T2SCCOMPRESSOROUTDOORFAN MOTORTHREE PHASEFIELD SUPPLYCAPACITORGROUNDINGLUGHIGH PRES.SWITCHCONTACTORT3L1L2L3GL1L
INSTALLATION / PERFORMANCE CHECK LISTELECTRICAL SYSTEM:Electrical connections tight? YES NOLine voltage polarity correct? YES NORated Voltage: _______
2 WARNING:The information listed below must be followed during the installation, service, and operation of this unit. Unqualified individuals should no
3AIR CONDITIONER INSTALLATIONGeneral InformationThe S4BD series air conditioner is designed only for outdoor rooftop or ground level installations. Th
4Connecting Refrigerant Tubing Between the Indoor & Outdoor Unit CAUTION:When servicing, cover or seal openings to minimize the exposure of the re
5• Overcurrentprotectionmustbeprovidedatthebranchcircuitdistributionpanelandsizedasshownontheunitrating label and according to appl
6Example:AB = 226VBC = 230VAC = 227V2. Determine the average voltage in the power supply.3. Determine the maximum deviation:4. Determine percent of vo
7Refrigerant Charging WARNING:S4BD Split System Air Conditioners are shipped charged with R410A refrigerant and ready for installation. If repairs mak
8Charging the Unit in AC mode at outdoor temperatures above55°Fforoptimizedsub-coolingof10°F-12°F.1. With the system operating at steady-st
9Suct.Press.OUTDOOR TEMPERATURE (°F)70 75 80 85 90 95 100 105Liq.Press.Dis.Temp.Liq.Press.Dis.Temp.Liq.Press.Dis.Temp.Liq.Press.Dis.Temp.Liq.Press.Dis