Form I-ADF, P/N 131805 R5, Page 1
Form I-ADF (Version A.3)
Obsoletes Form I-ADF (Version A.2)
Applies to: Indoor or Outdoor Gas, Direct-Fired,
Makeup Air/Heating Systems,
Model ADF and Model ADFH
Installation
Model ADF
!
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or
property damage.
Be sure to read and understand the installation, operation, and service instructions in
this manual.
Improper installation, adjustment, alteration, service, or maintenance can cause
serious injury, death, or property damage.
Do not store or use gasoline or other ammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a phone remote from the building. Follow
the gas suppliers instructions.
If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service agency,
or the gas supplier.

Przeglądanie stron 0
1 2 3 4 5 6 ... 27 28

Podsumowanie treści

Strona 1 - WARNING:

Form I-ADF, P/N 131805 R5, Page 1 Form I-ADF (Version A.3)Obsoletes Form I-ADF (Version A.2) Applies to: Indoor or Outdoor Gas, Direct-Fired, Makeup

Strona 2 - 1.1 Hazard Labels and Notices

Form I-ADF, Page 10

Strona 3 - 2.0 Location

Form I-ADF, P/N 131805 R5, Page 11 FIGURE 7 - Pressure Tap Locations for Measuring Manifold and Pilot PressureGas Pressure SwitchesGas pressure switch

Strona 4 - Dimensions

Form I-ADF, Page 12Installation Instructions (Refer to Air Hood Assembly Drawing in FIGURE 8B. All screw ends except those across the bottom should be

Strona 5 - 

Form I-ADF, P/N 131805 R5, Page 13 FIGURE 9A - O

Strona 6

Form I-ADF, Page 14FIGURE 11A - Factory-installed Evaporative Cooling Module Option on Models ADF/ADFH 300 and 500 Evaporative cooling provides exc

Strona 7 - 5. Mounting

Form I-ADF, P/N 131805 R5, Page 15 FIGURE 12 - Optional Evaporative Cooling Module on an ADF/ADFH 700 or 1200.Assembled module is shipped separately

Strona 8 - 5.0 Mounting

Form I-ADF, Page 16Thread bleed line tting (hose barb) into the adapter; attach a 1/4" hose.FIGURE 15 - Bleed Line FittingBleed Line Connection

Strona 9

Form I-ADF, P/N 131805 R5, Page 17 Filling & Adjusting the Water Level in the Reservoir Float and Pump Control System -- Turn on the water supply.

Strona 10 - (cont'd)

Form I-ADF, Page 186.0 Mechanical (cont'd)6.3 Supply Air Discharge6.3.1 Distribution of Makeup AirMakeup air can be introduced to the building ei

Strona 11 - 6.2 Unit Inlet Air

Form I-ADF, P/N 131805 R5, Page 19 Motor Pulleys and Blower Speed - Units are set at the factory for the RPM required to meet the CFM and external sta

Strona 12

Form I-ADF, Page 2WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury or death. Read the

Strona 13 - AW3, AW6, AW13

Form I-ADF, Page 20

Strona 14

Form I-ADF, P/N 131805 R5, Page 21 When a console with a dirty lter indicator is selected, the remote console includes a fourth light (dirty lter i

Strona 15

Form I-ADF, Page 22Optional Door SwitchOptional FirestatControl used for Outside Air Cutoff and Discharge Low Temperature Limit (Freezestat)9.0 Comm

Strona 16

Form I-ADF, P/N 131805 R5, Page 23 Check disconnect switch to be sure that it is tightly secured against the cabinet.If disconnect is fusible, check

Strona 17

Form I-ADF, Page 241. Prepare system for startup testing -- □ Attach a slope gauge (0 to 1.0" scale) to the tubing connections in the control com

Strona 18

Form I-ADF, P/N 131805 R5, Page 25 If the slope gauge reading is greater than -.25" (such as -.10" w.c.), adjust the drive to increase the b

Strona 19 - 7.0 Electrical and

Form I-ADF, Page 266. Check pilot pressure and operation --To check pilot gas pressure, connect a "U"-tube manometer to the pressure tap on

Strona 20 - Wiring (cont'd)

Form I-ADF, P/N 131805 R5, Page 27 DANGER: The gas burner in this direct gas-red system is designed and equipped to provide safe, complete combustion

Strona 21 - 8.0 Controls

Form I-ADF, Page 28www.ReznorHVAC.com; (800) 695-1901©2014 Reznor LLC, All rights reserved. Trademark Note: Reznor® is registered in at least the Unit

Strona 22 - 9.0 Commissioning

Form I-ADF, P/N 131805 R5, Page 3 1.2 General Description The information in this manual applies to Model ADF and Model ADFH in Sizes 300, 500, 700 an

Strona 23 - 

Form I-ADF, Page 43.1 Uncrating and InspectingCheck for any damage that may have been incurred during shipment. If damage is found, document the

Strona 24 - 9.0 Commisoning

Form I-ADF, P/N 131805 R5, Page 5 

Strona 25

Form I-ADF, Page 6

Strona 26

Form I-ADF, P/N 131805 R5, Page 7 Mounting is the responsibility of the installer. Depending on the building and its use, determine whether or not add

Strona 27 - F rise the CO

Form I-ADF, Page 8FIGURE 3 - Cross Support Mounting Requirements5.0 Mounting (

Strona 28 - Trademark Note: Reznor

Form I-ADF, P/N 131805 R5, Page 9 